With display
|
No
|
|
Voltage type for actuating
|
AC/DC
|
|
Rated operating voltage Ue
|
200 V
|
|
Rated control supply voltage at AC 50 Hz
|
24 V
|
|
Rated control supply voltage at AC 60 Hz
|
24 V
|
|
Overload current
|
12.3 A
|
|
Controller type
|
SMC-3
|
|
DV/DT protection
|
1000V/µs for power circuit
|
|
Repetitive peak voltage
|
1400V per UL/CSA/NEMA for power circuit
|
|
Operating frequency
|
50/60 Hz per UL/CSA/NEMA for power circuit
|
|
Line connected motor power, max
|
7.5 kW @ 230V AC, 50 Hz, 3-phase
|
|
Delta connected motor power, max
|
7.5...30 kW @ 380/400/415V AC, 50 Hz, 3-phase
|
|
Overvoltage category
|
III per IEC for side mount auxiliary contacts
|
|
Rated impulse voltage
|
6 kV for power circuit
|
|
Dielectric withstand
|
2500V AC per IEC for power circuit
|
|
Line connected motor current
|
12.3...37 A @ 380/400/415/460V AC, 3-phase
|
|
Delta connected motor current
|
21…64 A @ 380/400/415/460V AC, 3-phase
|
|
Insulation voltage
|
Rated 600V AC per UL/CSA/NEMA for power circuit
|
|
Rated operational voltage
|
250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
|
|
Rated control power during start with fan
|
215 mA @ 120V AC/180 mA @ 240V AC, 800 mA @ 24V DC/660 mA @ 24V AC
|
|
Input OFF-state current
|
<10 mA, <12 mA @ input OFF-state voltage (IN1, IN2) for control circuit
|
|
Short-circuit protection device list
|
Non-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
|
|
Number of contacts
|
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
|
|
High capacity available fault current, max
|
70 kA @ 600V, maximum current 60 A time delay Class J or Class L fuse for line connected motors
|
|
Type of current
|
TB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
|
|
Conventional thermal current (Ith)
|
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
|
|
Type of control circuit
|
TB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
|
|
Type of contacts
|
TB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
|
|
Utilization category
|
TB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
|
|
Rated operational current, max
|
TB-97, -98 (OVLD/Fault): 0.6 A @ 120V AC and 0.3 A @ 240V AC for auxiliary contacts
|
|
Standard controller feature
|
Soft stop
|
|
Standard available fault current, max
|
10 kA @ maximum standard fuse 250 A for delta device operational current rating
|
|
Rated control supply voltage at DC
|
24 V
|
|
Integrated motor overload protection
|
Yes
|
|
Short circuit protection device performance
|
Type 1
|
|
Selectable overload trip class
|
Trip Class 10, 15, or 20
|
|
Selectable start times
|
2, 5, 10, 15, 20, 25, or 30 s
|
|
Input OFF-state voltage (IN1, IN2), max
|
40V AC, 17V DC/12V AC for control circuit
|
|
Selectable current limit
|
150%, 250%, 350%, and 450% of full load current
|
|
Input ON-state voltage, during start (IN1, IN2)
|
85V AC, 19.2V DC/19.2V AC minimum for control circuit
|
|
Rated control power during start without fan
|
205 mA @ 120V AC/145 mA @ 240V AC, 705 mA @ 24V DC/580 mA @ 24V AC
|
|
Input ON-state current (IN1, IN2)
|
9.8 mA @ 120V AC/19.6 mA @ 240V AC for control circuit, 7.3 mA @ 24V AC/DC for control circuit
|
|
Degree of protection (IP)
|
IP2X
|
|
Weight
|
0.86 kg
|
|
Shock
|
Operational: 15 G
|
|
Width
|
44.8 mm (1.76 inch)
|
|
Depth
|
110 mm (4.33 inch)
|
|
Height
|
139.7 mm (5.5 inch)
|
|
Cable size
|
2.5...25 mm² (14...4 AWG) for line power terminals
|
|
Vibration
|
Operational: 1.0 G peak, 0.15 mm (0.006 inch) displacement
|
|
Make
|
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
|
|
Break
|
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
|
|
Tightening torque
|
2.3...3.4 Nm (30 lb.inch) for line power terminals, 4.0 Nm (35 lb.inch) if 25 mm² (4 AWG) wire in top terminal for line power terminal
|
|
Internal bypass
|
Yes
|
|
Function
|
Single direction
|
|
Selectable kick start - 450% FLA
|
0, 0.5, 1.0, or 1.5 s
|
|
Selectable initial torque
|
15%, 25%, 35%, and 65% of locked rotor torque
|
|
Selectable soft stop
|
Off, 100%, 200%, or 300% of the start time setting when wired
|
|
Steady state heat dissipation
|
24 W
|
|
Storage and transportation temperature
|
-25 °C
|
|
Rated surrounding temperature range without derating
|
-5 °C
|
|
Humidity
|
5...95% noncondensing
|
|
Operating temperature
|
Open: -5 to 50 °
|